Back to Raypak Guides

Raypak Digital Ignition Diagnostic Guide

PoolDial Equipment Library • Applies to: Digital 206A-406A, Digital Low NOx 207A-407A, Professional 268A-408A, X94/SR410, Above-Ground 106A-156A
Raypak Digital Ignition Diagnostic Guide

Looking for Raypak specs? See the linked Raypak equipment pages for electrical values, BTU ranges, and replacement parts.

Raypak Digital Ignition Diagnostic Guide

Raypak's Digital 206A-406A, Digital Low NOx ASME 207A-407A, Professional Atmospheric 408A, and Above-Ground 106A-156A manuals use the same atmospheric-heater diagnostic vocabulary. The Professional Series X94/SR-410 does not: its manual defines a newer error-message table with water-sensor, auxiliary-control, ignition-control, inducer, flue, and condensate faults. The sections below intentionally keep those controls separate.

Atmospheric-heater diagnostic readouts

These come from the status tables and control-logic flow charts for Digital, Low NOx, Professional 408A, and Above-Ground models.

Display ReadsManual-backed causeField check
"Sensor Failure," "Sensor Open," or "Sensor Short"Temperature sensor out of rangeInspect the thermistor, wires, and connector at Terminal P1. Check resistance against the chart. Replace the thermistor if not within 10% of chart values; if okay, replace the circuit board.
"Water Sw Open"Water flow/pressure switch issueVerify water flow and pressure. Clean the filter or strainer before condemning the switch.
"Hi Limit 1 Fault" / "Hi Limit 2 Fault"High limit switch openVerify water flow, inspect the internal thermostat and bypass valve. On ASME units this is a manual-reset device — press the MODE button to reset.
"Rollout Sw Open"Rollout sensor trippedCheck for a blocked heat exchanger or soot buildup, then press the manual reset button.
"Clock/Fireman Sw"Fireman or remote switch in the safety loop is OFFCheck the fireman switch or remote control wiring for an open condition.
"Vent/Field Sw #1"Vent switch openCheck connections to the board; if an extractor is installed, troubleshoot the extractor.
"Ignition Lockout"Pilot flame not established, or lost during trial for main burnerCheck power at the pilot valve, check for spark, and verify a clean pilot orifice with proper clearance from igniter to ground rod.
"Ignition Failure"Gas supply or valve operation issueVerify gas is reaching the heater and confirm valve operation.

X94 / SR-410 error messages

The X94/SR-410 table below comes from its Error Condition Messages table and troubleshooting flow chart. Do not translate these messages through the atmospheric-heater table above.

Display readsManual-backed causeField check
WPS Stuck Closed / Water Sw OpenThe water-flow switch does not match the current operating state.Verify pump operation, valve position, filter condition, and water flow before checking the switch.
H2O Sensor FailWater-temperature sensors are open, shorted, or disagree.Inspect the water-sensor circuits and wiring before replacing a sensor or control.
Aux Ctrl Fault 2 / 3 / 5 / 6 / 8Digital-control ROM, RAM, analog-reference, multiplexer, or clock fault.Record the exact number and follow the control-board diagnostic path in the current manual.
Ign Ctrl Fault 2 / 3 / 5 / 6 / 7Ignition-control ROM, RAM, analog, flame-sense, or execution fault.Record the exact number and have the ignition-control circuit diagnosed by qualified service.
Hi Water Temp / Hi Limit 1 Fault / Hi Limit 2 FaultWater exceeded 108°F or a high-limit circuit opened.Stop heating and check actual temperature, circulation, limits, sensor operation, and bypass condition before reset.
Blocked Vent / Vent Temp LimitThe vent safety or vent-temperature limit is open.Shut the heater down and have the vent path, switch circuit, and over-temperature cause inspected.
Air Flow Sw Open / Air Flow Sw Closed / Fan LockoutThe inducer airflow switch did not match the fan state; three fan-switch faults in one demand create lockout.Check the inducer, switch, tubing, relay, and wiring before clearing the lockout.
Ignition Failure / Ign 60 min Delay / Ignition LockoutFlame was not established within the permitted trial sequence.Verify fuel type and supply, gas-valve operation, ignition wiring, igniter, grounding, and flame proving through qualified service.
MV Output Fault / Flame w/o CFHThe gas-valve output is wrong or flame is sensed with the valve closed.Shut off gas and have the valve and ignition control inspected immediately.
Low Temp Lockout / Low VoltageWater is below 36°F, or control supply is below 20 V.Verify actual water temperature and have the low-voltage supply and transformer checked.
Flue Over Temp / Flue Sense Fail / Blocked DrainThe flue is too hot, its sensor failed, or the condensate-drain switch is closed.Shut the heater down and have venting, sensor wiring, combustion, and condensate drainage inspected.
Fan RPM FaultActual fan speed differs from target by more than 500 RPM.Check for obstruction, loose wiring, blower power, and motor-control operation through qualified service.
"EOL" at startupThe MODE button is stuck.Check the MODE button for a stuck or jammed switch.

Mechanical symptoms for the atmospheric models

SymptomManual-backed checks
Harmonics or whining noiseCheck U.G. (unitized gas valve) movement in hot water above 110°F. Look for debris or restriction in the water or gas line. Low flow can allow scale to form in the heat exchanger — check pool pH and total alkalinity.
Heater cycles on and off continuouslyClean or replace a dirty filter, raise a low pool water level, adjust the external bypass, or adjust an out-of-spec pressure switch.
Liming or scale forming in the exchangerCorrect pool water chemistry first. Inspect the bypass for movement and replace if none; replace the U.G. if it doesn't move when heated.
SootingReduce high flow rates with a manual bypass valve (target 105-110°F outlet). Check U.G. movement, air starvation, improper venting, and insects or debris clogging burner intake ports.
Pilot outage or "weak flame" signalAdjust low gas pressure, clean a restricted or dirty pilot, or replace a weak pilot generator.
Yellow, lazy flameAdjust low gas pressure and clean burner intake ports of insects or debris.
Takes too long to heat pool or spaConfirm the heater isn't undersized for the pool gallonage, reset the time clock for adequate filter run time, clean a dirty filter, and confirm the gas line/meter is sized correctly.
Leaking at well or heat exchanger, or brittle/leaking gasketOveracid water is the most common cause — correct water chemistry and replace the affected part. A gasket that's overheated because the heater runs after the pump shuts off points to the pressure switch adjustment.

Model Notes

  • Digital 206A-406A and Digital Low NOx ASME 207A-407A share nearly word-for-word diagnostic readout tables; the ASME line adds manual-reset language on Hi Limit faults.
  • Professional 268A-408A uses the same flow chart structure, routing "Sensor Failure," "Water Sw Open," and "Hi Limit Fault" through the same Diagnostic Readouts step.
  • Professional Series X94/SR-410 has a separate control vocabulary, documents the "EOL" stuck-MODE-button condition, and stores 10 faults accessible from the front touchpad.
  • Above-Ground 106A-156A covers both the P-106 and P-156 controls; the P-156 adds a full digital thermostat with the atmospheric Diagnostic Readouts structure.

Source: Raypak Digital 206A-406A, Digital Low NOx ASME 207A-407A, Professional Atmospheric 408A, Professional Series X94/SR-410, and Above-Ground 106A-156A installation and operation manuals. Confirm the rating-plate model and use the current manufacturer manual before service.

Related Raypak Guides